page_banner

ETD01 MCB main or MCCB main breaker three phase distribution board

ETD01 MCB main or MCCB main breaker three phase distribution board

MCB or mccb main breaker three phase distribution board.
Fully shrouded busbar/Pan assembly


  • Main incomer: MCB or mccb
  • Main incoming current: 125Amp
  • The distribution board divides the electrical power feed into subsidiary circuits, while providing a protective circuit breaker for each circuit in a common enclosure.

    What breaker can adapt for this board?
    Default: 1. Etechin manufactured breakers
    Others: 2. Schneider, ABB, GE,Simens, Legrand, Hager, China, Himel, Ls, Mitsubishi, Hitachi, Eletra brand made circuit breaker.

    Please advise us the breaker you will use in the distribution board

    In the worldwide, despite the adoption of a standard DIN rail for mounting and a standard cut-out shape, as the positions of the busbar/ terminal connections are not standardized.

    Product Detail

    Product Tags

    Feature

    1. Pan assembly KEMA approved
    2. Galvanized 1.2mm sheet
    3 .Main switch: MCB,ISOLATOR,ELCB,MCCB up to 250A
    4 .Outgoing: upto 72poles way MCB
    5. Plastic Lock/ Metal Lock
    6. Surface/flush type
    7. Adjusted mounting plate
    8. Powder coating Ral7035 texture
    9. IP42 for Metal Enclosure
    10. IEC61439-1

    Standard IEC61439-1&2, Designed to be operated by an ordinary person
    Pan assembly rating(A) 125,200,250A
    No.of phase 1,2,3
    Voltage Rating(V) 110-415
    Rated Insulation voltage(V)Ui 690V
    Mounting type Flush/Surface
    No. of ways(3phase) 4,6,8,10,12,14,16,18,20,22,24
    Ingress protection(IP) IP40
    Enclosure material Electro galvanized steel
    Steel sheet thickness(mm) 1&1.2mm
    Surface finishing Powder coated with electrostatic Epoxy polyester(RAL7035)
    Coating thickness 70-90 microns
    Main incomer breaker MCCB or MCB, ELCB+ISOLATOR,
    Branch breaker 1,2,3P din-rail type 18mm width MCB
    Neutral terminal Capacity Offer 10mm diameter lug hole
    Earth  terminal Capacity Offer 10mm diameter lug hole
    Ambient Temperature(℃) 30,50

    Dimension

    scsav

    The above dimension are for surface mounting type. Flush mounting type H and W add 20mm.
    Due to same brand incomer in big size, the final dimension should accord customer's breaker to revise if need.
    OEM/ ODM and customization are welcome.

    qrwqrq

    Main Factor effect Cost/Price:
    1.Thickness and kind of steel:
    2.Dimension of the board
    3.Structure of the board

    gqwqd

    Why choose us?

    As an experienced manufacturer in the low-voltage electric field, we specialize in manufacturing advanced circuit breakers, distribution boards and electric accessories.
    We own modern product lines, high quality testing equipment, scientific administration, professional engineers, highly-trained technicians and skilled workers. All these merits promote our products to tally meet the international standards. Our products sell well in more than 20 countries and regions around the world and gain a high reputation.
    Now, we have our own production lines of plastic injection, metal cutting, metal punching, metal bending, welding, powder coating.


  • Previous:
  • Next:

  • Write your message here and send it to us