ETM2 MCB
ETM2 Series is a high-performance Miniature Circuit Breaker (MCB) fully compliant with IEC 60898-1 standard, designed for overcurrent protection in residential, commercial, and light industrial electrical installations. It has the certification of Dekra / KEMA, CE and CB .
The rated current is related to different areausing for example one pole 10 to 16 ampere is normally used for lighting, 20 ampere to 33 ampere is normally used for kitchen andbathroom area, also used for air conditioner and other line equipment.
The electrical life can be up to 8000 operations and mechanical life up to 20000 operations, while the IEC requirement is only4000 operations and 10000 operations.
Product Introduction
| Basic features | |||
| Standards | EN/IEC 60898-1 | ||
| Certificate | Dekra/KEMA,CE,CB | ||
| Electrical features | |||
| Rated current in | A | 6, 10, 16, 20, 25, 32, 40, 50, 63 | |
| Rated voltage Ue | V | 230/400, 240/415 | |
| Rated frequency | Hz | 50/60 | |
| Number of poles | P | 1, 2, 3 | |
| Ultimate short-circuit breaking capacity Icu | kA | 6/10 | |
| Service short-circuit breaking capacity Ics | kA | 6kA(Icu 6kA),7.5kA(Icu 10kA) | |
| Rated insulation voltage Ui | V | 500 | |
| Rated impulse withstand voltage Uimp | kV | 4 | |
| Dielectric test voltage at ind. Freq. for 1 min | kV | 2 | |
| PoIIution degree | 2 | ||
| Trip form | Thermal magnetic trip | ||
| Magnetic release characteristic | B type(3-5In) | ■ | |
| C type(5-10In) | ■ | ||
| D type(10-20In) | ■ | ||
| Thermal release characteristic | 1.13In Non trip cold state | ≤ 63A t ≥ 1h | |
| 1.45In trip after 1.13 test | ≤ 63A t<1h | ||
| Mechanical features | |||
| Mechanical life | T | 10000 | |
| Electrical life | T | 4000 | |
| Reference temperature for setting of thermal element | ℃ | 30,40,50 | |
| Ambient temperature | ℃ | -35~+70℃ | |
| Installation | |||
| Degree of Protection | IP20 | ||
| Nominal cross-sectional area of the copper conductor | mm2 | 25 | |
| Tightening torque | N·m | 2.0 | |
| Line entry | Line-plug in,Load-cable | ||
| Mounting | Mount on plug in type Pan assembly/Busbar | ||
ETM2series MCB is in complied with IEC 60898-1 standard. It has the certification of Dekra / KEMA, CE and CB . The breaking capacity of ETM2 is 10KA, or 6KA. The rated current is (1A, 2A, 3A, 4A) 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A. The rated current is related to different areausing for example one pole 10 to 16 ampere is normally used for lighting, 20 ampere to 33 ampere is normally used for kitchen andbathroom area, also used for air conditioner and other line equipment.