ETM3RFS RCBO
ETM8RFS, 1P+N, RCBO, B, C curve, Residual Current Breaker with Over-Current protection, din rail
Manufacturer, OEM
Standards: IEC/EN61009-1
Rated current in: 6, 10, 16, 20, 25, 32, 40A
Sensitivity: 30mA, 100mA
Short circuit breaking capacity: 6 or 10KA
Voltage: AC 240/415V
Product Introduction
| Basic features | |||
| Standards | IEC/EN61009-1 | ||
| Certificate | Semko, CE, CB | ||
| Electrical features | |||
| Protection | Residual current, overload and short circuit | ||
| Rated current In | A | 6, 10, 16,20, 25, 32, 40 | |
| Rated residual operating current | mA | 10, 30, 100, 300 | |
| Residual current type | AC,A,AC-S,A-S | ||
| Rated voltage Ue | V | 230/240 | |
| Rated frequency | Hz | 50/60 | |
| Number of poles | P | 1P+N(1 Module) | |
| Ultimate short-circuit breaking capacity Icu | kA | 6, 10 | |
| Service short-circuit breaking capacity Ics | kA | 6kA(Icu 6kA),7.5kA(Icu 10kA) | |
| Rated insulation voltage Ui | V | 500 | |
| Rated residual current operated making &breaking capacity I △ m | A | 3000 | |
| Rated residual non-operated current I △ n | 0.5I △ n | ||
| Residual current off-time at I △ n | ≤ 0.1s,150~500ms(s type) | ||
| Rated impulse withstand voltage Uimp | kV | 4 | |
| PoIIution degree | 2 | ||
| Type of trip Residual current | Electronic | ||
| Type of Over current trip | Thermal-magnetic | ||
| Thermo-magnetic release characteristic | B type(3In~5In) | ■ | |
| C type(5In~10In) | ■ | ||
| Mechanical features | |||
| Mechanical life | T | 20000 | |
| Electrical life | T | 8000 | |
| Reference temperature for setting of thermal element | ℃ | 30, 40, 50 | |
| Ambient temperature | ℃ | -25 ~ +55℃ | |
| Installation | |||
| Protection degree | IP20 | ||
| Width | mm | 18 | |
| Terminal connection | Pillar terminal with frame | ||
| Terminal capacity | Line -25mm² ,Load -16mm² | ||
| Tighten torque | N·m | 2.0 | |
| Installation | on Din rail EN50022(35mm) | ||
ETM3RFS series RCBO are applicable to the low-voltage terminal distribution in the industry, civil building such as home and residence, energy, communication, infrastructure, lighting distribution system or motor distribution and other fields. They provide leakage protection, short-circuit protection, overload protection, and isolation protection, which can protect the human from hurting caused by leakage of current, at the main while they can protect the circuit and appliances from the secondary accident caused by overload and short circuit.
ETM3RFS series RCBO is in complied with IEC 61009-1standard.
The breaking capacity of ETM8LE is 10KA, or 6KA
The tripping type of short circuit is B, C curve.
The rated current is 6A, 10A, 16A, 20A, 25A, 32A, 40A.
The sensitivity current of Residual Current, or Earth Leakage tripping is 10mA, 30mA, 100mA, while 10mA and 30mA is mainly used in circuit of bath room and kitchen to protect the human from electric shock.
The tripping type of Residual current is AC or A class.
Rated voltage: 230V/ 240V ( Phase & Neutral)
There is a position indicator equipped on the products, Red is on, Green is off.
The RCBO terminals are IP20 protection which is designed for finger and hand touch safe to keep the safety during installation.
The ETM3RFS RCBO can work reliably in harsh environment, in ambient temperature from -5°C to 50°C.
The electrical life can be up to 8000 operations and mechanical life up to 20000 operations, while the IEC requirement is only 4000 operations and 10000 operations.
It’s mounting type is to be mounted on din rail EN50022 35mm.
Related Products