Product Introduction
| Basic features | ||||||||||||||||||||
| Standard | IEC 60947-2 | |||||||||||||||||||
| Electrical features | ||||||||||||||||||||
| Model | ETS6TA125 | ETS6TA160 | ETS6TA250 | ETS6TA400 | ETS6TA630 | ETS6TA800 | ||||||||||||||
| Rated current In | A | 16,20,25,30, 32,40,50,60, 63,70,75,80, 90,100,125 | 30,32,40,50,63,70, 75,80,100,125,140, 150,160 | 100,125,140, 150,160,175, 180,200,225, 250 | 250,280, 300,320,315, 350,400 | 400,500, 550,630 | 630,700,800 | |||||||||||||
| Rated operational voltage Ue | V | 380/400/415/690 | ||||||||||||||||||
| Number of poles | P | 3P / 4P | ||||||||||||||||||
| Rated insulation voltage | V | 800 | 1000 | |||||||||||||||||
| Breaking capacity | L | M | H | SH | L | M | H | SH | L | M | H | SH | M | H | M | H | M | H | ||
| Rated ultimate short-circuit breaking capacity(Icu) | kA | 18 | 25 | 40 | 55 | 18 | 30 | 40 | 65 | 18 | 30 | 40 | 70 | 55 | 75 | 55 | 80 | 55 | 90 | |
| Rated service short-circuit breaking capacity(Ics) | kA | 10 | 18 | 30 | 40 | 10 | 20 | 30 | 50 | 10 | 20 | 30 | 50 | 40 | 50 | 40 | 55 | 40 | 60 | |
| Rated impulse withstand voltage Uimp | kV | 8KV | 8KV | 8KV | 8KV | 8KV | 12KV | |||||||||||||
| Mechanical life | 10000 | 10000 | 10000 | 8500 | 8500 | 4000 | ||||||||||||||
| Electrical life | 5000 | 5000 | 5000 | 3000 | 3000 | 1000 | ||||||||||||||
| Arc distance | mm | ≤ 50 | ≤ 50 | ≤ 100 | ≤ 100 | ≤ 100 | ≤ 100 | |||||||||||||
| Auxiliary contact(OF) | ■ | ■ | ■ | ■ | ■ | ■ | ||||||||||||||
| Alam swith(SD) | ■ | ■ | ■ | ■ | ■ | ■ | ||||||||||||||
| Shunt trip(MX) | ■ | ■ | ■ | ■ | ■ | ■ | ||||||||||||||
| Under-voltage release(MN) | ■ | ■ | ■ | ■ | ■ | ■ | ||||||||||||||
| Motor-Mechanism | ■ | ■ | ■ | ■ | ■ | ■ | ||||||||||||||
| Outside size (mm) + Z +2 | 3P | L | 75 | 75 | 92 | 92 | 107 | 107 | 140 | 181 | 210 | |||||||||
| W | 132 | 132 | 155 | 155 | 165 | 165 | 257 | 270 | 280 | |||||||||||
| H1 | 67 | 78 | 74 | 95 | 76 | 94 | 112 | 110 | 116 | |||||||||||
| H2 | 82 | 93 | 92 | 112 | 100 | 117 | 148 | 155 | 155 | |||||||||||
| 4P | L | 100 | 100 | 123 | 123 | 143 | 143 | 187 | 240 | 280 | ||||||||||
| W | 132 | 132 | 155 | 155 | 165 | 165 | 258 | 270 | 280 | |||||||||||
| H1 | 67 | 78 | 74 | 95 | 76 | 94 | 112 | 110 | 116 | |||||||||||
| H2 | 82 | 93 | 92 | 113 | 100 | 117 | 148 | 155 | 155 | |||||||||||
ETS6TA series of circuit breakers are new upgraded circuit breakers researched and developed by the company combined with theadvantages of similar international products and demand of domestic and international markets.
With insulation voltage up to 1000V, the circuit breaker is applicable for distribution systems of AC50Hz, rated working voltage690V and rated working current from 10A to800A, used to distribute electric power energy, protect circuits and power equipmentagainst overload, short circuit, under voltage and so on, also can be used for infrequent startup of motor and protect it fromoverload, short circuit or under voltage.It is featured with small size, high breaking, short flash over, etc., is the ideal product for users. It can be verticallyinstalled or horizontally installed.ETS6 series DC Molded case circuit breaker (hereinafter referred to as circuit breaker) is suitable for DC systems of ratedvoltage up to and including DC 1000V and rated current 10~800A, used to distribute electric power energy, protect circuits andpower equipment against overload, short circuit and so on.The products can be fed with wires from top and bottom, and it is polarity-free.
It complies with the standards IEC60947-2, GB14048.2, etc. Feature 1: current limiting capacity
With insulation voltage up to 1000V, the circuit breaker is applicable for distribution systems of AC50Hz, rated working voltage690V and rated working current from 10A to800A, used to distribute electric power energy, protect circuits and power equipmentagainst overload, short circuit, under voltage and so on, also can be used for infrequent startup of motor and protect it fromoverload, short circuit or under voltage.It is featured with small size, high breaking, short flash over, etc., is the ideal product for users. It can be verticallyinstalled or horizontally installed.ETS6 series DC Molded case circuit breaker (hereinafter referred to as circuit breaker) is suitable for DC systems of ratedvoltage up to and including DC 1000V and rated current 10~800A, used to distribute electric power energy, protect circuits andpower equipment against overload, short circuit and so on.The products can be fed with wires from top and bottom, and it is polarity-free.
It complies with the standards IEC60947-2, GB14048.2, etc. Feature 1: current limiting capacity
Feature 2: modularized accessories
Feature 3:miniaturized frame
Feature 4: contact repulsion device (patented technology)
Related Products